SF6 gas and U.S. greenhouse gas emissions

The use of sulfur-hexafluoride (SF6) gas globally has been the subject of a large amount of discussion for many years, both in the U.S., and worldwide. SF6 is recognized as an extremely potent greenhouse gas, primarily because of its atmospheric lifetime of about 3,200 years, with a global warming potential (GWP) of 22,800 years. The reference gas for GWP values is CO2, which is assigned a GWP of 1.0. The EPA considers SF6 as the most potent greenhouse gas that they have investigated.1

SF6 was introduced in the 1950s in electrical equipment, and was quickly adopted for high-voltage outdoor circuit breakers, particularly above 38 kV. It ultimately lead to obsolescence of oil circuit breakers, and also of air-blast circuit breakers. The early gas-filled circuit breakers in the high-voltage arena had relatively high leakage rates, and hence a relatively large amount of SF6 was released into the atmosphere. Exacerbating this situation was the common practice when maintenance of these circuit breakers was needed that involved removal of the gas from the circuit breaker, some users simply released the gas to the atmosphere instead of recovering the gas for recycling and/or reuse.2

About the same time that users and manufacturers became sensitive to the environmental impact of simply releasing the gas, substantial rises in the cost of SF6 gas took place, so users and manufacturers had a real economic interest in conserving the gas and reusing it. Both factors led to a very substantial reduction in the amount of gas released to the environment.3

The data indicates that emissions by manufacturers have remained at a low level through the period of 1990-2013, with emissions by users declining by 80 percent in the same period, with much of the reduction occurring in the 1990-2009 period.

Over time, information on the nature of SF6 as a greenhouse gas became available, and designs for the circuit breakers were improved. Today, many designs for products that use SF6 gas (for insulation only-not for interruption) have leakage rates of the order of 0.1 percent per gas compartment per year, far lower than leakage rates of historic products. For circuit breakers that use SF6 gas for insulation and interruption, the leakage rate of present designs is under 0.5 percent per year.

For a more extensive discussion of SF6 and its properties, and usage in metal-enclosed, medium-voltage switchgear, refer to TechTopics No. 53.

On April 15, 2015, the U.S. Environmental Protection Agency released a report entitled “Inventory of U.S. Greenhouse Gas Emissions and Sinks: 1990-2013”. This report contains a great deal of information (564 pages), but the information in the report that relates to SF6 gas is quite interesting.4

The data indicates that the largest share of greenhouse gas net emissions in 2013 is from combustion of fossil fuels, accounting for approximately 77 percent of total GWPweighted emissions. Of this value, about 40 percent of the CO2 from fossil fuel combustion came from use of fossil fuels for generation of electricity.5

The report indicates that total net emissions of SF6 in 2013 were 6.9 MMT CO2-equivalent (million metric tons CO2-equivalent), of which net emissions in electrical transmission and distribution were 5.1 MMT CO2-equivalent and the remainder of the emissions were from magnesium production and processing and from semiconductor manufacture.6

Also for 2013, total emissions and sinks (i.e., net emissions) of greenhouse gases were reported as 5,791.2 MMT CO2-equivalent. Therefore, net emissions of SF6 comprised 5.1/5791.2 = 0.088 percent (less than 0.1 percent) of total net emissions in the U.S.7

Total net emissions for 1990 were shown as 5,525.2 MMT CO2-equivalent, and the emissions of electrical transmission and distribution were 25.4 MMT CO2-equivalent.

Thus, the data shows that the emissions from electrical transmission and distribution declined 79.9 percent from 1990 to 2013!

The EPA report supports the opinion that emissions of SF6 gas from modern designs of high-voltage and medium-voltage switchgear and circuit breakers is not a significant factor in global warming and climate change.

Switchgear and circuit breaker manufacturers have been researching alternatives to SF6 gas for many years, but this work has not resulted in a suitable substitute.

At this time, there is no indication that the U.S. EPA will restrict the use of SF6 in electrical equipment. The California Air Resources Board (CARB) has mandated that leakage of SF6 be reduced to one percent in 2020. The Siemens types 8DA and 8DB medium-voltage, gas-insulated switchgear designs, with a leakage rate of less than 0.1 percent per year, are already below the 2020 limits mandated by CARB.

CARB also instituted inventory reporting requirements for owners of SF6 or equipment using SF6, applicable to owners with 17,800 lbs of SF6. 17,800 lbs of SF6 gas is about the amount of gas in 2,700 units of single-bus type 8DA switchgear, or about 1,400 units of double-bus type 8DB switchgear.

There are no known efforts to impose a tax on SF6 usage. The Australian government enacted such a tax in 2013 but rescinded the tax in mid-2014.


References

Legal Disclaimer

TechTopics are published for informational purposes only. Siemens
makes no guaranty of accuracy or applicability to any specific customer
projects or applications, and assumes no responsibility for the readers’
use of this information. Siemens recommends that anyone seeking to
use this information in field operations consult with or verify its
applicability through an independent qualified professional.
The information provided in this document contains merely general
descriptions or characteristics of performance which in case of actual
use do not always apply as described or which may change as a result of
further development of the products. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the terms
of contract.

All product designations may be trademarks or product names of
Siemens AG or supplier companies whose use by third parties for their
own purposes could violate the rights of the owners.

Siemens Industry, Inc.
7000 Siemens Road
Wendell, NC 27591

Subject to change without prior notice.
Order No.: IC1000-F320-A267-X-4A00
All rights reserved.
© 2015 Siemens Industry, Inc.
For more information, contact: +1 (800) 347-6659

Did this information help you?