Technical Data

SPD Specifications

  • Surge Current Rating Per Phase

Per Phase

L-N

L-G

N-G

100kA

50kA

50kA

50kA

150kA

100kA

50kA

50kA

200kA

100kA

100kA

100kA

250kA

150kA

100kA

100kA

300kA

150kA

150kA

150kA

400kA

200kA

200kA

200kA

500kA

250kA

250kA

250kA

  • 100% monitoring – Every MOV is monitored, incl. N-G

  • Individually fused and thermally protected MOV’s

  • Solid state bi-directional operation

  • EMI/RFI filtering: Active tracking up to -50db from 10kHz to 100MHz

  • Repetitive impulse: 5,000 hits

  • Less than 1 nanosecond response time

  • Relative humidity range: 0 -95% non-condensing

  • Operating frequency: 47-63Hz

  • Operating temperature: -25°C (-15°F) to +60°C (140°F)